Overview
ZRP321 can quickly respond to open flames generated by the combustion of hydrocarbons, while eliminating a large number of false alarm sources, providing continuous protection for fire warning. BSV931 adopts a dual channel design, which can simultaneously monitor real fire and the infrared radiation generated by surrounding environmental interference. Combined with advanced flame recognition algorithms, it can achieve rapid response of open flame detection while effectively eliminating false alarm sources
Key Features
- Excellent anti-interference ability, able to effectively eliminate false alarm sources;
- Excellent Anti-EMC ability, able to effectively shield EMC interference;
- Large window design, capable of achieving 90 ° wide area coverage;
- Long distance flame recognition, with a maximum detection distance of up to 50 meters.
Applications
Large storage facilities, production workshops, industrial parks, petrochemicals, charging stations, material storage yards, etc
Technical Specifications
| Model | ZRP321 |
| Detection object | Hydrocarbon combustion |
| Operating voltage | 12V |
| Operating current | ≤10mA |
| Output signal | UART |
| Operating environment | Temperature: -10~55°C |
| Humidity: 15%~90% RH (without condensation) | |
| Detecting distance | 45±5m( n-heptane, 0.3m*0.3m, analytical grade) |
| Response time | 1-10 seconds, used in non-interference environments and fast alarm situations; 10-20 seconds, used in less interference environments and reliable alarm situations; 20-30 seconds, used in complex interference environments and reliable alarm situations; |