BSV481 Pyro-electric Flame sensor module

SKU: BSV481 Category:

Overview

BSV481 is a flame detection module based on the infrared and ultraviolet principle. It uses pyroelectric sensors, ultraviolet sensor and high-performance microprocessors. It is a flame detection module designed through the combination of different sensors. It has a built-in high-speed microcontroller to collect sensor signals and use reliable and efficient algorithms to effectively judge the fire. The interface is simple and the output signals are complete. Simply design a simple power circuit and relay circuit to develop a complete flame detector, shortening the product development cycle.

Key Features

  • Adopt large field of view angle, high detection rate, and low microphone effect sensor;
  • The ultraviolet sensor has a sun blind type, effectively reducing sunlight interference;
  • Combining multiple combustion substances to establish a data model with low false alarm rate;
  • M4 core high-speed microcontroller with fast response and low power consumption.

Applications

Space industry, storage facilities, printing industry, paint manufacturing, pharmaceutical industry, power generation facilities, machinery and automobile manufacturing, petroleum and petrochemical industry, etc.

Technical Specifications

Model BSV481
Detection object Combustion of hydrocarbons and non carbonaceous substances
Spectral range IR4.48um~5.0um, UV185-260nm
Operating voltage 5V (Carrying capacity not less than 2A)
Operating current ≤40mA
Interface level 0~3.3V
Output signal High and low levels can be used to drive relays
PWM, can be used as a 4-20mA control signal
Operating environment Temperature: -10~55°C
Humidity: 15%~90% RH (without condensation)
Dimension Ø56mm*H21.5mm
Response time Four levels are represented by the number of green LED flashes, with the green light flashing every 3 seconds representing the alarm time level. Level I: 6-10 seconds, used in non-interference environments and fast alarm situations; Level II: 15-18 seconds, used in non-interference environments and reliable alarm situations; Level III: 22-26 seconds, used in environments with interference and reliable alarm situations; Level IV: 3-4 seconds, used to demonstrate rapid alarms.
Adjust method Magnetic rod adjustment
Detecting distance [email protected]*0.3m(Fuel: n-heptane)
Logic judgment OR Logic