Product Details & Specifications
BLX Emergency UPS Function Switching Power Supply 60W-350W
The PSC Series is a switching power supply with integrated battery charging and UPS function, providing zero-transfer-time backup power and stable DC output. It serves industrial automation (PLC, servo drives, CNC), communication infrastructure (base stations, servers), security & transportation (traffic signals, surveillance, RVs), renewable energy & smart grids (energy storage, EV charging), medical equipment, building automation, and other mission-critical applications. With intelligent battery management and support for CAN, Modbus, RS485, it ensures non-stop operation, data loss prevention, and easy integration.
|
PSC-60UPS/Charge Function Switching Power Supply
|
|||||
|
Project
|
Technicalindicators
|
||||
|
Model
|
PSC-60-12
|
PSC-60-24
|
|||
|
Output |
DC voltage
|
CH1:13.8V
|
CH2:13.8V
|
CH1:27.6V
|
CH2 :27.6V
|
|
Output voltage
tolerance |
±1%
|
——–
|
±1%
|
——–
|
|
|
Rated current
|
3.5A
|
1A(Charge)
|
1.5A
|
0.7A(Charge)
|
|
|
Ripple and noise
|
150mVp-p
|
——-
|
200mVp-p
|
——–
|
|
|
rated power
|
60W
|
60W
|
|||
|
Output current range
|
0-4.5A
|
——–
|
0-4.5A
|
——-
|
|
|
DC voltage adjustable
range |
CH1:11.3-14.9V
|
CH1:21.3-29.8V
|
|||
|
Start,rise,hold time
|
600ms,50ms,80ms:230VAC ,
1200ms,50ms,16ms:115VAC |
600ms,50ms 80ms:230VAC,
1200ms,50ms 16ms:115VAC |
|||
|
Input
|
voltage range
|
90-264VAC 47-63HZ;135VDC~370VDC
|
|||
|
Efficiency(typical)
|
>88%
|
>88%
|
>88%
|
>88%
|
|
|
Working current
|
115VAC<1.8A ,230VAC <0.9A
|
||||
|
pulse current
|
110VAC 25A,230VAC 40A
|
||||
|
Start,rise,hold time
|
|||||
|
Protect
|
Overload protection
|
When the output rated power is>105%-115%:Protection mode:
hiccup mode,it can automatically recover after the abnormal conditions are removed. |
|||
|
Battery low voltage
protection |
9.5~10.3V,Protection mode,cut off output
|
19~20.5V,Protection mode,cut off output
|
|||
|
Environment
|
Working temperature,
humidity |
-20C~+60°℃,20%~90RH
|
|||
|
Storage temperature
and humidity |
-20C~+85℃,10%~95RH
|
||||
|
Function
|
UPS
|
Long-term online float charging of the battery,high charging
efficiency,battery fullness can be as high as 97% or more |
|||
|
Automatically stops when fully charged to prevent battery
overcharging and effectively extend battery life |
|||||
|
Automatic mains/battery switching,no switching time,no need for human supervision.
|
|||||
|
Cold start function,when there is no mains power,the UPS can be started directly with the battery to meet the user’s emergency needs
|
|||||
|
Safety
regulations |
Protection mode,cut
off output |
Input and output:1.5KVAC,1 minute
|
|||
|
solation resistor
|
Input and output,input shell,output shell:500VDC/100MQ
|
||||
|
Other
|
size
|
129*97*30mm
|
|||
|
Net weight/gross weight
|
0.38KG/0.42KG
|
||||
|
PSC-100UPS/Charge Function Switching Power Supply
|
|||||
|
Project
|
Technicalindicators
|
||||
|
Model
|
PSC-100-12
|
PSC-100-24
|
|||
|
Output |
DC voltage
|
CH1:13.8V
|
CH2:13.8V
|
CH1:27.6V
|
CH2 :27.6V
|
|
Output voltage
tolerance |
±1%
|
——–
|
±1%
|
——–
|
|
|
Rated current
|
5A
|
2A(Charge)
|
2.5A
|
1A(Charge)
|
|
|
Ripple and noise
|
150mVp-p
|
——-
|
200mVp-p
|
——–
|
|
|
rated power
|
100W
|
100W
|
|||
|
Output current range
|
0-7A
|
——–
|
0-3.5A
|
——-
|
|
|
DC voltage adjustable
range |
CH1:11.3-14.9V
|
CH1:21.3-29.8V
|
|||
|
Start,rise,hold time
|
600ms 50ms80ms :230VAC ,
1200ms 50ms16ms :115VAC |
600ms 50ms 80ms:230VAC,
1200ms 50ms 16ms:115VAC |
|||
|
Input
|
voltage range
|
90-264VAC 47-63HZ;135VDC~370VDC
|
|||
|
Efficiency(typical)
|
>87%
|
>87%
|
>87%
|
>87%
|
|
|
Working current
|
115VAC<2.4A ,230VAC <1.2A
|
||||
|
pulse current
|
110VAC 30A,230VAC 50A
|
||||
|
Start,rise,hold time
|
100ms 30ms 21ms:110VAC ,100ms 30ms 100ms:
220VAC |
||||
|
Protect
|
Overload protection
|
When the output rated power is>105%-115%:Protection mode:
hiccup mode,it can automatically recover after the abnormal conditions are removed. |
|||
|
Battery low voltage
protection |
9.5~10.3V,Protection mode,cut off output
|
19~20.5V,Protection mode,cut off output
|
|||
|
Environment
|
Working temperature,
humidity |
-20C~+60°℃,20%~90RH
|
|||
|
Storage temperature
and humidity |
-20C~+85℃,10%~95RH
|
||||
|
Function
|
UPS
|
Long-term online float charging of the battery,high charging
efficiency,battery fullness can be as high as 97% or more |
|||
|
Automatically stops when fully charged to prevent battery
overcharging and effectively extend battery life |
|||||
|
Automatic mains/battery switching,no switching time,no need for human supervision.
|
|||||
|
Cold start function,when there is no mains power,the UPS can be started directly with the battery to meet the user’s emergency needs
|
|||||
|
Safety
regulations |
Protection mode,cut
off output |
Input and output:1.5KVAC,1 minute
|
|||
|
solation resistor
|
Input and output,input shell,output shell:500VDC/100MQ
|
||||
|
Other
|
size
|
129*97*30mm
|
|||
|
Net weight/gross weight
|
0.38KG/0.42KG
|
||||
|
PSC-150UPS/Charge Function Switching Power Supply
|
|||||
|
Project
|
Technicalindicators
|
||||
|
Model
|
PSC-150-12
|
PSC-150-24
|
|||
|
Output |
DC voltage
|
CH1:13.8V
|
CH2:13.8V
|
CH1:27.6V
|
CH2 :27.6V
|
|
Output voltage
tolerance |
±1%
|
——–
|
±1%
|
——–
|
|
|
Rated current
|
7.5A
|
3A(Charge)
|
4A
|
1.5A(Charge)
|
|
|
Ripple and noise
|
150mVp-p
|
——-
|
200mVp-p
|
——–
|
|
|
rated power
|
150W
|
152W
|
|||
|
Output current range
|
0-10.5A
|
——–
|
0-5.5A
|
——-
|
|
|
DC voltage adjustable
range |
CH1:11.3-14.9V
|
CH1:21.3-29.8V
|
|||
|
Start,rise,hold time
|
600ms 50ms 80ms:230VAC ,
1200ms 50ms 16ms:115VAC |
600ms 50ms 80ms:230VAC,
1200ms 50ms 16ms:115VAC |
|||
|
Input
|
voltage range
|
90-264VAC 47-63HZ;135VDC~370VDC
|
|||
|
Efficiency(typical)
|
>87%
|
>87%
|
>89%
|
>89%
|
|
|
Working current
|
115VAC<3.2A ,230VAC <1.6A
|
||||
|
pulse current
|
110VAC 30A,230VAC 50A
|
||||
|
Protect
|
Overload protection
|
When the output rated power is>105%-115%:Protection mode:
hiccup mode,it can automatically recover after the abnormal conditions are removed. |
|||
|
Battery low voltage
protection |
9.5~10.3V,Protection mode,cut off output
|
19~20.5V,Protection mode,cut off output
|
|||
|
Environment
|
Working temperature,
humidity |
-20C~+60°℃,20%~90RH
|
|||
|
Storage temperature
and humidity |
-20C~+85℃,10%~95RH
|
||||
|
Function
|
UPS
|
Long-term online float charging of the battery,high charging
efficiency,battery fullness can be as high as 97% or more |
|||
|
Automatically stops when fully charged to prevent battery
overcharging and effectively extend battery life |
|||||
|
Automatic mains/battery switching,no switching time,no need for human supervision.
|
|||||
|
Cold start function,when there is no mains power,the UPS can be started directly with the battery to meet the user’s emergency needs
|
|||||
|
Safety
regulations |
Protection mode,cut
off output |
Input and output:1.5KVAC,1 minute
|
|||
|
solation resistor
|
Input and output,input shell,output shell:500VDC/100MQ
|
||||
|
Other
|
size
|
159*97*30mm
|
|||
|
Net weight/gross weight
|
0.47KG/0.55KG
|
||||
|
PSC-250UPS/Charge Function Switching Power Supply
|
|||||
|
Project
|
Technicalindicators
|
||||
|
Model
|
PSC-250-12
|
PSC-250-24
|
|||
|
Output |
DC voltage
|
CH1:13.8V
|
CH2:13.8V
|
CH1:27.6V
|
CH2 :27.6V
|
|
Output voltage
tolerance |
±1%
|
——–
|
±1%
|
——–
|
|
|
Rated current
|
14.5A
|
3.5A(Charge)
|
6.5A
|
2.5A(Charge)
|
|
|
Ripple and noise
|
150mVp-p
|
——-
|
200mVp-p
|
——–
|
|
|
rated power
|
250W
|
250W
|
|||
|
Output current range
|
0-18A
|
——–
|
0-9A
|
——-
|
|
|
DC voltage adjustable
range |
CH1:11.3-14.9V
|
CH1:21.3-29.8V
|
|||
|
Start,rise,hold time
|
600ms 50ms 80ms:230VAC ,
1200ms 50ms 16ms:115VAC |
600ms 50ms 80ms:230VAC,
1200ms 50ms 16ms:115VA |
|||
|
Input
|
voltage range
|
90-264VAC 47-63HZ;135VDC~370VDC
|
|||
|
Efficiency(typical)
|
>87%
|
>87%
|
>89%
|
>89%
|
|
|
Working current
|
115VAC<4.5A ,230VAC <2.5A
|
||||
|
pulse current
|
110VAC 45A,230VAC 55A
|
||||
|
Protect
|
Overload protection
|
When the output rated power is>105%-115%:Protection mode:
hiccup mode,it can automatically recover after the abnormal conditions are removed. |
|||
|
Battery low voltage
protection |
9.5~10.3V,Protection mode,cut off output
|
19~20.5V,Protection mode,cut off output
|
|||
|
Environment
|
Working temperature,
humidity |
-20C~+60°℃,20%~90RH
|
|||
|
Storage temperature
and humidity |
-20C~+85℃,10%~95RH
|
||||
|
Function
|
UPS
|
Long-term online float charging of the battery,high charging
efficiency,battery fullness can be as high as 97% or more |
|||
|
Automatically stops when fully charged to prevent battery
overcharging and effectively extend battery life |
|||||
|
Automatic mains/battery switching,no switching time,no need for human supervision.
|
|||||
|
Cold start function,when there is no mains power,the UPS can be started directly with the battery to meet the user’s emergency needs
|
|||||
|
Safety
regulations |
Protection mode,cut
off output |
Input and output:1.5KVAC,1 minute
|
|||
|
solation resistor
|
Input and output,input shell,output shell:500VDC/100MQ
|
||||
|
Other
|
size
|
215*115*30mm
|
|||
|
Net weight/gross weight
|
0.75KG/0.82KG
|
||||
|
PSC-350UPS/Charge Function Switching Power Supply
|
|||||
|
Project
|
Technicalindicators
|
||||
|
Model
|
PSC-350-12
|
PSC-350-24
|
|||
|
Output |
DC voltage
|
CH1:13.8V
|
CH2:13.8V
|
CH1:27.6V
|
CH2 :27.6V
|
|
Output voltage
tolerance |
±1%
|
——–
|
±1%
|
——–
|
|
|
Rated current
|
20A
|
5A(Charge)
|
10A
|
2.5A(Charge)
|
|
|
Ripple and noise
|
150mVp-p
|
——-
|
200mVp-p
|
——–
|
|
|
rated power
|
345W
|
350W
|
|||
|
Output current range
|
0-18A
|
——–
|
0-9A
|
——-
|
|
|
DC voltage adjustable
range |
CH1:11.3-14.9V
|
CH1:21.3-29.8V
|
|||
|
Start,rise,hold time
|
600ms 50ms, 80ms:230VAC ,
1200ms,50ms,16ms:115VAC |
600ms,50ms,80ms:230VAC,
1200ms 50ms 16ms:115VAC |
|||
|
Input
|
voltage range
|
90-264VAC 47-63HZ;135VDC~370VDC
|
|||
|
Efficiency(typical)
|
>87%
|
>87%
|
>89%
|
>89%
|
|
|
Working current
|
115VAC<6.5A ,230VAC <3.5A
|
||||
|
pulse current
|
110VAC 45A,230VAC 55A
|
||||
|
Protect
|
Overload protection
|
When the output rated power is>105%-115%:Protection mode:
hiccup mode,it can automatically recover after the abnormal conditions are removed. |
|||
|
Battery low voltage
protection |
9.5~10.3V,Protection mode,cut off output
|
19~20.5V,Protection mode,cut off output
|
|||
|
Environment
|
Working temperature,
humidity |
-20C~+60°℃,20%~90RH
|
|||
|
Storage temperature
and humidity |
-20C~+85℃,10%~95RH
|
||||
|
Function
|
UPS
|
Long-term online float charging of the battery,high charging
efficiency,battery fullness can be as high as 97% or more |
|||
|
Automatically stops when fully charged to prevent battery
overcharging and effectively extend battery life |
|||||
|
Automatic mains/battery switching,no switching time,no need for human supervision.
|
|||||
|
Cold start function,when there is no mains power,the UPS can be started directly with the battery to meet the user’s emergency needs
|
|||||
|
Safety
regulations |
Protection mode,cut
off output |
Input and output:1.5KVAC,1 minute
|
|||
|
solation resistor
|
Input and output,input shell,output shell:500VDC/100MQ
|
||||
|
Other
|
size
|
215*115*30mm
|
|||
|
Net weight/gross weight
|
0.85KG/0.95KG
|
||||