BLX Emergency UPS Function Switching Power Supply 60W-350W

SKU: BX-PWR-17704 Category:

Product Details & Specifications

BLX Emergency UPS Function Switching Power Supply 60W-350W
The PSC Series is a switching power supply with integrated battery charging and UPS function, providing zero-transfer-time backup power and stable DC output. It serves industrial automation (PLC, servo drives, CNC), communication infrastructure (base stations, servers), security & transportation (traffic signals, surveillance, RVs), renewable energy & smart grids (energy storage, EV charging), medical equipment, building automation, and other mission-critical applications. With intelligent battery management and support for CAN, Modbus, RS485, it ensures non-stop operation, data loss prevention, and easy integration.
PSC-60UPS/Charge Function Switching Power Supply
Project
Technicalindicators
Model
PSC-60-12
PSC-60-24

Output

DC voltage
CH1:13.8V
CH2:13.8V
CH1:27.6V
CH2 :27.6V
Output voltage
tolerance
±1%
——–
±1%
——–
Rated current
3.5A
1A(Charge)
1.5A
0.7A(Charge)
Ripple and noise
150mVp-p
——-
200mVp-p
——–
rated power
60W
60W
Output current range
0-4.5A
——–
0-4.5A
——-
DC voltage adjustable
range
CH1:11.3-14.9V
CH1:21.3-29.8V
Start,rise,hold time
600ms,50ms,80ms:230VAC ,
1200ms,50ms,16ms:115VAC
600ms,50ms 80ms:230VAC,
1200ms,50ms 16ms:115VAC
Input
voltage range
90-264VAC 47-63HZ;135VDC~370VDC
Efficiency(typical)
>88%
>88%
>88%
>88%
Working current
115VAC<1.8A ,230VAC <0.9A
pulse current
110VAC 25A,230VAC 40A
Start,rise,hold time
Protect
Overload protection
When the output rated power is>105%-115%:Protection mode:
hiccup mode,it can automatically recover after the abnormal conditions are removed.
Battery low voltage
protection
9.5~10.3V,Protection mode,cut off output
19~20.5V,Protection mode,cut off output
Environment
Working temperature,
humidity
-20C~+60°℃,20%~90RH
Storage temperature
and humidity
-20C~+85℃,10%~95RH
Function
UPS
Long-term online float charging of the battery,high charging
efficiency,battery fullness can be as high as 97% or more
Automatically stops when fully charged to prevent battery
overcharging and effectively extend battery life
Automatic mains/battery switching,no switching time,no need for human supervision.
Cold start function,when there is no mains power,the UPS can be started directly with the battery to meet the user’s emergency needs
Safety
regulations
Protection mode,cut
off output
Input and output:1.5KVAC,1 minute
solation resistor
Input and output,input shell,output shell:500VDC/100MQ
Other
size
129*97*30mm
Net weight/gross weight
0.38KG/0.42KG
PSC-100UPS/Charge Function Switching Power Supply
Project
Technicalindicators
Model
PSC-100-12
PSC-100-24

Output

DC voltage
CH1:13.8V
CH2:13.8V
CH1:27.6V
CH2 :27.6V
Output voltage
tolerance
±1%
——–
±1%
——–
Rated current
5A
2A(Charge)
2.5A
1A(Charge)
Ripple and noise
150mVp-p
——-
200mVp-p
——–
rated power
100W
100W
Output current range
0-7A
——–
0-3.5A
——-
DC voltage adjustable
range
CH1:11.3-14.9V
CH1:21.3-29.8V
Start,rise,hold time
600ms 50ms80ms :230VAC ,
1200ms 50ms16ms :115VAC
600ms 50ms 80ms:230VAC,
1200ms 50ms 16ms:115VAC
Input
voltage range
90-264VAC 47-63HZ;135VDC~370VDC
Efficiency(typical)
>87%
>87%
>87%
>87%
Working current
115VAC<2.4A ,230VAC <1.2A
pulse current
110VAC 30A,230VAC 50A
Start,rise,hold time
100ms 30ms 21ms:110VAC ,100ms 30ms 100ms:
220VAC
Protect
Overload protection
When the output rated power is>105%-115%:Protection mode:
hiccup mode,it can automatically recover after the abnormal conditions are removed.
Battery low voltage
protection
9.5~10.3V,Protection mode,cut off output
19~20.5V,Protection mode,cut off output
Environment
Working temperature,
humidity
-20C~+60°℃,20%~90RH
Storage temperature
and humidity
-20C~+85℃,10%~95RH
Function
UPS
Long-term online float charging of the battery,high charging
efficiency,battery fullness can be as high as 97% or more
Automatically stops when fully charged to prevent battery
overcharging and effectively extend battery life
Automatic mains/battery switching,no switching time,no need for human supervision.
Cold start function,when there is no mains power,the UPS can be started directly with the battery to meet the user’s emergency needs
Safety
regulations
Protection mode,cut
off output
Input and output:1.5KVAC,1 minute
solation resistor
Input and output,input shell,output shell:500VDC/100MQ
Other
size
129*97*30mm
Net weight/gross weight
0.38KG/0.42KG
PSC-150UPS/Charge Function Switching Power Supply
Project
Technicalindicators
Model
PSC-150-12
PSC-150-24

Output

DC voltage
CH1:13.8V
CH2:13.8V
CH1:27.6V
CH2 :27.6V
Output voltage
tolerance
±1%
——–
±1%
——–
Rated current
7.5A
3A(Charge)
4A
1.5A(Charge)
Ripple and noise
150mVp-p
——-
200mVp-p
——–
rated power
150W
152W
Output current range
0-10.5A
——–
0-5.5A
——-
DC voltage adjustable
range
CH1:11.3-14.9V
CH1:21.3-29.8V
Start,rise,hold time
600ms 50ms 80ms:230VAC ,
1200ms 50ms 16ms:115VAC
600ms 50ms 80ms:230VAC,
1200ms 50ms 16ms:115VAC
Input
voltage range
90-264VAC 47-63HZ;135VDC~370VDC
Efficiency(typical)
>87%
>87%
>89%
>89%
Working current
115VAC<3.2A ,230VAC <1.6A
pulse current
110VAC 30A,230VAC 50A
Protect
Overload protection
When the output rated power is>105%-115%:Protection mode:
hiccup mode,it can automatically recover after the abnormal conditions are removed.
Battery low voltage
protection
9.5~10.3V,Protection mode,cut off output
19~20.5V,Protection mode,cut off output
Environment
Working temperature,
humidity
-20C~+60°℃,20%~90RH
Storage temperature
and humidity
-20C~+85℃,10%~95RH
Function
UPS
Long-term online float charging of the battery,high charging
efficiency,battery fullness can be as high as 97% or more
Automatically stops when fully charged to prevent battery
overcharging and effectively extend battery life
Automatic mains/battery switching,no switching time,no need for human supervision.
Cold start function,when there is no mains power,the UPS can be started directly with the battery to meet the user’s emergency needs
Safety
regulations
Protection mode,cut
off output
Input and output:1.5KVAC,1 minute
solation resistor
Input and output,input shell,output shell:500VDC/100MQ
Other
size
159*97*30mm
Net weight/gross weight
0.47KG/0.55KG
PSC-250UPS/Charge Function Switching Power Supply
Project
Technicalindicators
Model
PSC-250-12
PSC-250-24

Output

DC voltage
CH1:13.8V
CH2:13.8V
CH1:27.6V
CH2 :27.6V
Output voltage
tolerance
±1%
——–
±1%
——–
Rated current
14.5A
3.5A(Charge)
6.5A
2.5A(Charge)
Ripple and noise
150mVp-p
——-
200mVp-p
——–
rated power
250W
250W
Output current range
0-18A
——–
0-9A
——-
DC voltage adjustable
range
CH1:11.3-14.9V
CH1:21.3-29.8V
Start,rise,hold time
600ms 50ms 80ms:230VAC ,
1200ms 50ms 16ms:115VAC
600ms 50ms 80ms:230VAC,
1200ms 50ms 16ms:115VA
Input
voltage range
90-264VAC 47-63HZ;135VDC~370VDC
Efficiency(typical)
>87%
>87%
>89%
>89%
Working current
115VAC<4.5A ,230VAC <2.5A
pulse current
110VAC 45A,230VAC 55A
Protect
Overload protection
When the output rated power is>105%-115%:Protection mode:
hiccup mode,it can automatically recover after the abnormal conditions are removed.
Battery low voltage
protection
9.5~10.3V,Protection mode,cut off output
19~20.5V,Protection mode,cut off output
Environment
Working temperature,
humidity
-20C~+60°℃,20%~90RH
Storage temperature
and humidity
-20C~+85℃,10%~95RH
Function
UPS
Long-term online float charging of the battery,high charging
efficiency,battery fullness can be as high as 97% or more
Automatically stops when fully charged to prevent battery
overcharging and effectively extend battery life
Automatic mains/battery switching,no switching time,no need for human supervision.
Cold start function,when there is no mains power,the UPS can be started directly with the battery to meet the user’s emergency needs
Safety
regulations
Protection mode,cut
off output
Input and output:1.5KVAC,1 minute
solation resistor
Input and output,input shell,output shell:500VDC/100MQ
Other
size
215*115*30mm
Net weight/gross weight
0.75KG/0.82KG
PSC-350UPS/Charge Function Switching Power Supply
Project
Technicalindicators
Model
PSC-350-12
PSC-350-24

Output

DC voltage
CH1:13.8V
CH2:13.8V
CH1:27.6V
CH2 :27.6V
Output voltage
tolerance
±1%
——–
±1%
——–
Rated current
20A
5A(Charge)
10A
2.5A(Charge)
Ripple and noise
150mVp-p
——-
200mVp-p
——–
rated power
345W
350W
Output current range
0-18A
——–
0-9A
——-
DC voltage adjustable
range
CH1:11.3-14.9V
CH1:21.3-29.8V
Start,rise,hold time
600ms 50ms, 80ms:230VAC ,
1200ms,50ms,16ms:115VAC
600ms,50ms,80ms:230VAC,
1200ms 50ms 16ms:115VAC
Input
voltage range
90-264VAC 47-63HZ;135VDC~370VDC
Efficiency(typical)
>87%
>87%
>89%
>89%
Working current
115VAC<6.5A ,230VAC <3.5A
pulse current
110VAC 45A,230VAC 55A
Protect
Overload protection
When the output rated power is>105%-115%:Protection mode:
hiccup mode,it can automatically recover after the abnormal conditions are removed.
Battery low voltage
protection
9.5~10.3V,Protection mode,cut off output
19~20.5V,Protection mode,cut off output
Environment
Working temperature,
humidity
-20C~+60°℃,20%~90RH
Storage temperature
and humidity
-20C~+85℃,10%~95RH
Function
UPS
Long-term online float charging of the battery,high charging
efficiency,battery fullness can be as high as 97% or more
Automatically stops when fully charged to prevent battery
overcharging and effectively extend battery life
Automatic mains/battery switching,no switching time,no need for human supervision.
Cold start function,when there is no mains power,the UPS can be started directly with the battery to meet the user’s emergency needs
Safety
regulations
Protection mode,cut
off output
Input and output:1.5KVAC,1 minute
solation resistor
Input and output,input shell,output shell:500VDC/100MQ
Other
size
215*115*30mm
Net weight/gross weight
0.85KG/0.95KG